5315 53 Ave
Twenty20 & Co Inc
elements
|
|
May 7, 2026 |
|
|
5315 53 Ave Cary , North Carolina |
|
|
Attached |
|
|
Partly Sunny |
|
|
Agent & Client |
|
|
Randy Bickle |
|
|
Lucy Rhinheart NA lucyR@gmail.com 9195523642 |
|
|
Na |
|
5:42PM Start Time |
method
This inspection is a visual, non-invasive review using normal controls & accessible areas.
We follow a consistent path through all major systems. Findings are structured for clarity so you understand what’s there, what needs attention & what to do next.
Each item lists the component or system, issue defect, recommended action & summary note.
Built to eliminate doubt.
"Turning information into decisions you can trust."
thank you
Thank you for choosing us for your inspection. We truly appreciate your trust.
I will be your primary contact & will do everything I can to ensure you are completely clear on today’s findings.
Please feel free to reach out at any time if you have questions or need further clarification. We’re always happy to help.
Kind Regards,
Randy Bickle
stuff.
A property inspection evaluates visible, non-exhaustive conditions & records findings in report form Inspectors examine readily accessible systems & components using a visual, non-invasive method & operate equipment using normal controls when possible. Components, issues, actions, location, trade & summary may be noted. Conditions reflect time of inspection only. Inaccessible or unsafe areas are not inspected (not accessible)
⚠️ We encourage you to read our Standards of Practice (SOP’s), scope, disclamers & limitations. The SOPs outline the scope of the inspection, the systems reviewed & the limitations that apply. They provide the framework inspectors follow to evaluate properties & communicate findings consistently. This structure helps ensure inspections are performed using a clear, proven, nationally recognized standard. Full details by clicking the logo. 🔻🔻🔻
The difference between something good and something great is attention to detail.
legends
![]() |
It’s a snap! Here are some key terms you’ll see throughout. |
| Iconography | Used for clarity. |
![]() |
Immediate Attention |
![]() |
Attention |
| Not Inspected | Limitations. |
| Hand Gestures | Universal. |
| Issue: | Identify the problem if there is one |
| Action: | Recommended path to address the issue |
| L: | Location where it is found |
| T: | Typical Tradesperson |
| R: | Reason why it wasn't inspected |
| $ / $$ / $$$ |
summary
Action: Clean / Repair / Maintain
Notes: Further evaluation by a pest control company
Action: Repair &/or Replace
Notes: A 100% if you don’t take care of stealing these screws, there’s gonna be water coming into your attic and then they’ll you’ll have mould
Action: Clean / Repair / Maintain L: Throughout
Notes: If you don’t fix this water will build up. You will have ice jam, and most likely water will come in through your foundation. Further evaluation by a structural engineer.
Action: Clean / Repair / Maintain
Notes: This is significant and you need a structural engineer to come over here and pin it
summary
Action: Clean / Repair / Maintain L: Front
Notes: This is just really bad installation and dents. Inside of docs are really bad and should be reinstalled by professional. Really bad installation.
Action: Seal / Repair / Monitor L: Front
Notes: 100% this is woodpecker damage and water will be coming in through your clotting and cause mould and more damage down the line
Action: Improve / Re-Grade
Notes: You have negative slope and erosion and if you don’t take care of this water will definitely come into your basement and cause nothing but problems in the future
Action: Repair &/or Replace
Notes: This box is unprotected and resting may occur if not repainted.
summary
Action: Clean / Repair / Maintain
Notes: This is really poor quality workmanship, and this should be rectified by a professional insulator. If not, you will have mould in your attic from conditioner. Attic rain is very costly.
Action: Install &/or Replace L: Cliset
Notes: Add a catch weatherstripping is compressed and it’s giving you a poor seal. If you do not rectify this, the potential for mould is great.
Action: Further Evaluate / Repair
Notes: If you do not rectify this, you will face the consequences of a potential shock or death
Action: Improve / Secure
Notes: Sagging and rubbing Doors often means major settlement and should be further evaluated by structural engineer.
summary
Action: Fix / Restore Function
Notes: Observation – Issue(s) should be monitored; plan for maintenance or correction as needed. This is a poor installation. You should ask for money off.
Action: Improve / Secure
Notes: Observation – Issue(s) should be monitored; plan for maintenance or correction as needed. If you don’t fix this, it could be very, very, very costly and no doubt you will have mold.
Reason: Missing / Not Installed: Item was fully absent or not installed where typically expected during a standard inspection.
Action: Further Evaluate / Repair
Notes: Immediate Attention – Issue(s) are critical or unsafe; corrective action required. This may result in significant damage and/or injury if not addressed.
summary
Action: Further Evaluate / Repair
Notes: Immediate Attention – Issue(s) are critical or unsafe; corrective action required. This may result in significant damage and/or injury if not addressed. Firehazard!!
Action: Repair &/or Replace
Notes: Observation – Issue(s) should be monitored; plan for maintenance or correction as needed.
Action: Further Evaluate / Repair
Notes: Immediate Attention – Issue(s) are critical or unsafe; corrective action required. This may result in significant damage and/or injury if not addressed. Your house could explode.
summary
Action: Improve / Secure
Notes: Immediate Attention – Issue(s) are critical or unsafe; corrective action required. This may result in significant damage and/or injury if not addressed.
Action: Improve / Secure
Notes: If you don’t fix this, this could really turn into something bad in the future because of bad humidity and it might end up causing you costly repairs and severe consequences
| R BACK TO SUMMARY |
|
|
|
|
|
Roof Observation - (2)
⠀ ⠀
|
|
|
|
Support Photo
|
|
|
|
|
|
|
|
|
| E BACK TO SUMMARY |
|
Report Legend
Explains reports symbols.
|
|
|
|
Window(s) & Trim-Casing
Reviewed for glazing, condition, cracking, flashing, gaps & sealant deterioration.
|
|
|
|
Exterior Outlet(s).
Inspected for safety, GFCI presence (using a standard plug tester.)
Exterior Faucet(s)
Inspected for location, flashings, sealant, operability, anti-siphon & leakage.
|
|
|
|
Additional Vent(s)
⠀⠀⠀⠀⠀⠀⠀⠀
|
|
|
|
|
|
|
|
|
|
|
⚠️ SLOPE & Grade Management
Proper grading should slope away from the foundation, not remain flat or create negative slope that directs water toward the property. Watch for heaving, settling, and high or low spots that can trap moisture near walls. Ensure downspouts discharge well away from the structure and that gutters are level and draining correctly. Poor alignment or overflow can erode soil over time, increasing the risk of moisture intrusion and foundation movement.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Grading & Drainage Baseline
Inspection of grading, pathways, flatwork, and drainage focused on visible slope, surface condition, and water flow around the structure. Limited to observable conditions at time of inspection.
|
|
|
|
|
Focus Feature Page
These are photos related to the same component or system.
|
|
|
|
Electrical Entry.
Observations include service attachment, drip loop, clearance & visible damage or corrosion
|
|
|
Power Down, Save Up.
To boost energy efficiency, switch to LED lighting and turn off lights when not in use. Use ceiling fans and set thermostats a few degrees higher in summer and lower in winter. Unplug electronics when not in use and choose ENERGY STAR® appliances. Lower your water heater to 120°F and insulate hot water pipes. Keep filters clean and schedule regular maintenance on heating and cooling systems.
|
|
|
|
⚠️ Exterior General Notes
1. Cladding: Visible fading, discoloration, and general wear from exposure.2. Trim / Sealants: Weathering consistent with age. 5. Flatwork: Typical settlement, discoloration, and signs of wear from use. 6. Grade: High - Low spots, erosion, and signs of movement. Monitor for improper drainage. |
|
|
|
The Exterior Baseline
𝗘𝘅𝘁𝗲𝗿𝗶𝗼𝗿 – 𝗔𝗿𝗲𝗮𝘀 𝗜𝗻𝘀𝗽𝗲𝗰𝘁𝗲𝗱Exterior components and finishes are reviewed for presence, general condition, visible damage, and basic operation where applicable. This includes commonly accessible elements such as exterior walls and cladding, doors and windows, trim and sealants, decks, steps, railings, porches, balconies, and visible foundation surfaces. Drainage features, surface grading, and other exterior elements that may affect moisture management and overall performance are also visually reviewed where present. |
|
| A BACK TO SUMMARY |
|
Report Legend
Explains reports symbols.
|
|
|
|
|
|
|
Sheathing / Roof Decking
Observations include material type, fastening pattern, visible sagging or deflection, moisture staining, delam & signs of past or active deterioration.
|
|
|
|
Insulation - Depth
Observations included insulation depth, vapour barrier presence, coverage consistency, & visible gaps. See also Insurance Section.
|
|
|
|
⚠️ Attic General Notes.
1. Structure: Surface variation as seen from hatch entry. Typical for age of property.
|
|
| I BACK TO SUMMARY |
|
Report Legend
Explains reports symbols.
|
|
|
|
Interior Light(s)
Inspected for operation using normal switching procedures & visible deficiencies.
|
|
|
|
Door Hinges
|
|
|
|
Interior Window(s) ⠀
Observations included glazing, operation, seals, & conditions affecting performance.
Window(s) & Operation
Review for opening, closing, latching, seals, weep holes & screens. See also Insurance Section.
|
|
|
General Ceilings / Walls
Visually examined for common defects.
|
|
|
|
|
|
|
|
Outside patio
|
|
|
|
|
|
|
|
The Fireplace Baseline
Components are reviewed for presence, general condition, and visible signs of damage or deterioration where accessible. This includes the fuel type, firebox, hearth, mantel, damper, and visible portions of the chimney and flue. Accessible areas are checked for soot accumulation, creosote buildup, cracks, or moisture intrusion. The review is limited to observable conditions without dismantling components or conducting internal chimney inspections.
|
|
|
|
|
|
|
|
The Interior Baseline
𝗜𝗻𝘁𝗲𝗿𝗶𝗼𝗿 – 𝗔𝗿𝗲𝗮𝘀 𝗜𝗻𝘀𝗽𝗲𝗰𝘁𝗲𝗱Interior components and finishes are reviewed for presence, general condition, visible damage, and basic operation where applicable. This includes commonly accessible areas and systems such as entry spaces, walls, ceilings, floors, trim, doors, windows, stairs, electrical components, lighting, life safety devices, heating and cooling distribution elements, and other visible interior features typically found within the living space of the home. |
|
| K BACK TO SUMMARY |
|
Report Legend
Explains reports symbols.
|
|
|
|
Kitchen Outlet(s)
Inspected for secure mounting, GFCI protection, polarity, grounding, cover condition & visible wiring concerns affecting safe use.
Microwave(s) ⠀
Missing / Not Installed: Item was fully absent or not installed where typically expected during a standard inspection.. Not Inspected
|
|
|
|
|
|
|
|
Stovetop(s) / Cooktop(s)
Inspected for basic operation, burner function, surface condition & safety concerns.
Oven(s)
Inspected for operation, interior condition, door sealing & visible safety concerns.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| L BACK TO SUMMARY |
|
Report Legend
Explains reports symbols.
|
|
|
+ |
Laundry Washer Machine
Reviewed, focused on plumbing connections, hoses, drains, seals & visible leakage.
|
|
|
|
Laundry Dryer(s).
People belongings inside. Not Inspected
|
| + | + |
|
|
|
|
|
| B BACK TO SUMMARY |
|
Report Legend
Explains reports symbols.
|
|
|
|
|
| + |
|
Plumbing Floor Drain(s)
|
|
|
|
Bathroom Water Faucet(s)
Operated to assess function, flow, mounting, sealing & signs of leakage, corrosion, or wear.
Sink Drain(s)
Forgot photo.
|
|
|
Bathroom P-Trap(s)
Checked for drainage, trap configuration, connection security, leakage indicators & visible corrosion.
|
|
|
|
Toilet(s)
Reviewed for stability, operation & visible leakage. X3 flush test per unit.
|
|
|
|
General Ceilings / Walls
Visually examined for common defects.
|
|
|
|
General Flooring
Visually examined for common defects.
|
|
|
|
Bathtub & Surround(s)
Inspected for condition, secure installation, functional drainage, faucet operation, and visible signs of leaks, cracks, damage, or deteriorated sealant at accessible areas.
|
|
| + |
|
|
|
|
Bathroom Ventilation
Bathroom exhaust fans help remove excess moisture created during bathing and showering. Running the fan during use and for at least 15–20 minutes afterward helps reduce humidity, which can prevent condensation, microbial growth, peeling finishes, and moisture damage to walls, ceilings, and nearby materials. Regular use and periodic cleaning of the fan grille improve performance and indoor air quality.
|
|
|
|
The Bathroom Baseline
Components are reviewed for presence, general condition, and visible signs of damage or deterioration where accessible. This includes cabinetry, countertops, sinks, faucets, visible plumbing, appliances, wall and ceiling finishes, and electrical receptacles. Accessible areas are checked for leaks, staining, loose or damaged finishes, improper clearances, and signs of moisture intrusion. The review is limited to observable conditions without moving appliances, dismantling components, or evaluating concealed plumbing, electrical, or ventilation systems.
|
|
| M BACK TO SUMMARY |
|
Report Legend
Explains reports symbols.
|
|
|
|
Electrical Panel(s) ⠀
Assessing breakers, wires, bond, 30" clearance, corrosion & damage. See also Insurance Section.
The Main AMP
Generally, this will shut down everything! Designed to interrupt a large amperage load.
|
|
|
|
Hot Water Data
Unit detail(s). See also Insurance Section.
|
|
|
+ |
|
|
|
|
Heating Unit Shutoff
Observed for accessibility, labeling, secure mounting & operation affecting emergency shutoff capability.
Water Main Shutoff ⠀
Assessing valve operation & signs of leakage, corrosion, or damage. See also Insurance Section. Peoples stuff in the way. Not Inspected
|
|
|
|
Plumbing Waterlines
Inspected for support, connections, leaks & visible corrosion or damage. See also Insurance Section.
|
|
|
Maintenance Advisory
Mechanical systems require routine homeowner maintenance and periodic observation for safe operation. This includes replacing heating system filters as recommended, keeping drains and condensate lines clear of debris, and periodically having sewer lines evaluated by a qualified contractor. Safety measures include maintaining domestic hot water at a safe temperature and installing locking or spring-loaded cover plates on critical controls to prevent accidental shutoff. Occupants should be familiar with all system shutoffs and label them clearly. Mechanical rooms should not be used for storage due to required clearance to combustibles. Homeowners should periodically check the mechanical room for calcification, minor leaks, corrosion, or unusual odors that may indicate developing issues.
|
|
|
|
General Ceilings / Walls
Visually examined for common defects.
|
|
|
|
|
|
|
|
Framing 101
Behind every wall is a framework — much like your own skeleton. Vertical studs form the bones, while cripples support around openings. King and jack studs work together to hold up headers over doors and windows, spreading the load. Top plates cap the walls and tie everything together, while bottom plates anchor it all to the floor. This unseen structure is critical to the strength, stability, and alignment of your home. Just like a healthy body depends on solid bones, your home depends on this framing to stand true. ⠀⠀⠀⠀⠀ ⠀ ⚠️ See also Insurance section for more details on your the structural specifications of this property.
|
|
|
|
|
|
| + |
|
|
insurance
| Safety Overview | |
| Site Limitations | n/a |
| Inspection Type | ◻️ Pre-Purchase Inspection (non-exhaustive) |
| Property Vacancy | |
| Smoke & CO | ⚠️ Not Verified: Unable to confirm function |
| Egress Windows | ⚠️ Location: Bedroom(s): Partially Present |
| Stairs & Handholds | ◻️ Structure: Functioning as Intended |
| Roof System | |
| Method of Inspection | ◻️ Ladder at edge (multiple locations) |
| Roofing Surface | |
| Drainage Path | ◻️ System: Trough & Downspouts |
| Ventilation System | ◻️ Box Vent(s) - Soffit |
| Exterior Overview | |
| Cooling Type(s) | n/a |
| Main Fuel Shutoff | ◻️ Location: Front Yard |
| Envelope Cladding | ◻️ Material: Wood |
| Steps & Guards | |
| Barriers & Walls | n/a |
| Grade & Ground Cover | ◻️ Terrain: Flat & Level - Vegitation |
| Hardscape Surfaces | ◻️ Material: Paths: Concrete - Drive: Concrete |
| Garage Systems | |
| Fire Seperation | n/a |
| Safety Auto Reverse | n/a |
| Heating Equipment | ◻️ Unit: Not Present |
| Attic System | |
| Hatch & Insulation | ◻️ Location: Prime Closet - Mat: Blown-In |
| Sheathing & Poly | ◻️ Material: OSB - Vap Barrier: Present (ltd vis) |
insurance
| Interior Overview | |
| Thermostat Location | ◻️ Location: Lower Level - Restored to original |
| Walls & Ceilings | ◻️ Material: Drywall |
| Flooring Surfaces | |
| Other Features |
| Kitchen & Bathroom | |
| Safety - GFCI’s | ◻️ Location: Kitchen: Present - Bath: Present |
| Ventilation System | ◻️ Type: Range Hood: to EXT. - B-Fan: Present |
| Laundry Specs |
| Mechanical System | |
| Heating Unit(s) | ◻️ Type: Mid E Furnace / Forced Air - Age:#### |
| Heating Fuel Source | ◻️ Type: Natural Gas - Primary |
| Water Heater Unit | ◻️ Type: Tank - Age:#### |
| Water Heating Fuel | ◻️ Type: Natural Gas - Primary |
| Plumbing System | ◻️ Public Water: Copper - City Sewer: ABS |
| Water Main Shutoff | ⚠️ Location: Undetermined |
| Back Flow Valve | ⚠️ Installation: Unknown |
| Electrical Service | ◻️ Entry: Overhead - Material: Aluminum |
| Service Disconnect | |
| Main Panel Interior | ◻️ Location: Mech Room - Ground: Unknown |
| Electrical System | ◻️ Service: 100 AMP - Branch: Copper |
| Structure System | |
| Roof Structure | ◻️ Type: Rafter Framing |
| Exterior Wall System | |
| Structure System | ◻️ Type: Dimensional Wood Frame |
| Foundation System | ◻️ Type: Poured Concrete |
| Structural Observ. | ◻️ Notes: No Movement |