703 Crimson Close

Twenty20 & Co Inc

Report Cover Image
the-details.png
703 Crimson Close Jun 25, 2026 at 5:31pm MDT

Jun 25, 2026

"Designed to tell the real story."

the summary

⚠️ Tap Here

the insurance

⚠️ Property Specs

quick-inspect.png Inspectagram Barcode
the

elements

Elements Image
Element Icon

Jun 25, 2026

Element Icon

703 Crimson Close

Calgary, Alberta

Element Icon

Attached

Element Icon

Partly Sunny +15°

Element Icon

Site Super (Kyle)

Element Icon

Lucas Kirsch MHI, MHB
Pre-Occ Inspection
Complete & Sent 5:11 PM

Element Icon

UBG Builders Group

Not Applicable

jim@UBR.com

4038365528

Element Icon

Not Applicable

Element Icon

4:10PM Start Time

the

method

Method Image

This inspection is a visual, non-invasive review using normal controls & accessible areas.

We follow a consistent path through all major systems. Findings are structured for clarity so you understand what’s there, what needs attention & what to do next.

Each item lists the component or system, issue defect, recommended action & summary note.

Built to eliminate doubt.

"Turning information into decisions you can trust."

Thank You Image

thank you

Thank you for choosing us for your inspection. We truly appreciate your trust.

I will be your primary contact & will do everything I can to ensure you are completely clear on today’s findings.

Please feel free to reach out at any time if you have questions or need further clarification. We’re always happy to help.

Kind Regards,

Lucas Kirsch

Lucas Kirsch

4038365528
reachme+lucas@2020mhi.com

disclaimer

stuff.

A

A property inspection evaluates visible, non-exhaustive conditions & records findings in report form Inspectors examine readily accessible systems & components using a visual, non-invasive method & operate equipment using normal controls when possible. Components, issues, actions, location, trade & summary may be noted. Conditions reflect time of inspection only. Inaccessible or unsafe areas are not inspected (not accessible)

⚠️ We encourage you to read our Standards of Practice (SOP’s), scope, disclamers & limitations. The SOPs outline the scope of the inspection, the systems reviewed & the limitations that apply. They provide the framework inspectors follow to evaluate properties & communicate findings consistently. This structure helps ensure inspections are performed using a clear, proven, nationally recognized standard. Full details by clicking the logo. 🔻🔻🔻

The difference between something good and something great is attention to detail.

icons &

legends

Lengend Icon It’s a snap! Here are some key terms you’ll see throughout.
Iconography Used for clarity.
Lengend Icon
Lengend Icon
Not Inspected Limitations.
Hand Gestures Universal.
Issue: Identify the problem if there is one
Action: Recommended path to address the issue
L: Location where it is found
T: Typical Tradesperson
R: Reason why it wasn't inspected
$ / $$ / $$$
the

summary

Exterior
attention icon
Exterior Outlet(s). :

The front exterior outlet showed an open ground/open neutral condition. Missing protection may contribute to shock or equipment damage. Recommend repair or replacement by a qualified electrician.

attention icon
Exterior Faucet(s) :

The garage exterior faucet was not functioning and no water was available. Continued use may result in further issues if left uncorrected. Recommend evaluation and repair by a qualified plumber.

attention icon
HVAC Utility Vent(s):

The HVAC utility vent at the balcony was missing sealant and had exposed areas. This may affect long-term performance. Recommend sealing and monitoring by a qualified general contractor.

attention icon
Additional Vent(s):

An additional vent at the balcony was missing its hood/component. This may impact performance if left uncorrected. Recommend installation or replacement by a qualified general contractor.

attention icon
Cladding / Material(s):

Minor areas of missing bondo/paint were observed on the cladding throughout. Cosmetic wear may gradually deteriorate over time. Recommend sealing and repairs during routine maintenance.

the

summary

Garage
attention icon
⚠️ Garage General Notes :

Garage general notes were provided for reference. Review the observation details and address noted items as appropriate.

Interior
attention icon
Heat Register(s):

Construction debris was present within the heat registers serving all ducts. Accumulated debris may reduce cleanliness over time. Recommend cleaning as part of routine maintenance.

Kitchen
attention icon
Kitchen P-Trap(s):

The right kitchen sink P-trap was loose or unsecured. This may allow leakage or moisture-related damage if left uncorrected. Recommend securing the assembly by a qualified plumber.

the

summary

Bathroom
attention icon
Bathroom Extraction Fan(s):

The main bathroom exhaust fan was not operating. Reduced ventilation may continue until corrected. Recommend repair or replacement by a qualified HVAC technician.

attention icon
Bathroom Sink Drain(s):

The main bathroom sink drained slowly and the stopper was set too low. Drainage performance may continue to be affected. Recommend repair or adjustment by a qualified plumber.

Mechanical
attention icon
Hot Water Unit(s) ⠀:

Minor rust was observed at the bottom of the hot water unit in the mechanical room. The condition should be monitored as part of routine maintenance. Recommend cleaning or repair by a qualified plumber if needed.

Roof
11
R BACK TO SUMMARY


Roof Observations - (1) RIDGE
Reviewing condition, flashings, drainage flow, debris, & intrusion points. See also Insurance Section.


Roof Observation (2) LOWER
⠀ ⠀

Roof Observation - (3) BOXES
⠀ ⠀ ⠀


Projection Observ. - (4) METAL
⠀ ⠀ ⠀

Gutter(s) -Trough(s)
Inspected for debris, drainage flow, interior condition and visible standing water.


Soffit(s) & Fascia(s)
Attn. given to ventilation openings, attachment, clearance & visible staining or obstructions.

Roof +
12
SOLID BUILD! ⭐️⭐️⭐️⭐️⭐️


Roof +
13
⚠️ Roof Observations
1. Surface Materials: Wear consistent with climate & exposure.
2. Sealants: Shrinkage & deterioration noted at penetrations.
3. Gutters/Drains: Minor granule accumulation noted.
4. Hidden Areas: Concealed roofing components not fully visible.
5. Roof Utilities: Minor surface wear noted.
End Statement:
Routine maintenance and inspections are recommended, including cleaning gutters and reviewing roof materials from inside the attic. Seasonal or annual tune-ups are encouraged to replace damaged or aging segments.

Exterior
14
E BACK TO SUMMARY


Exterior Entry Door(s)
Inspected for condition, glazing, sealing, flashing, alignment & operation. SLIGHT RUBBING


Window(s) & Trim-Casing
Reviewed for glazing, condition, cracking, flashing, gaps & sealant deterioration.

Exterior Outlet(s).
Inspected for safety, GFCI presence (using a standard plug tester.) Open Ground / Open Neutral. Repair &/or Replace.


Exterior Faucet(s)
Inspected for location, flashings, sealant, operability, anti-siphon & leakage. No Function / No water. Further Evaluate / Repair.

HVAC Utility Vent(s)
Inspected for installation, fittings, clearances, penetrations & sealant condition. Missing Sealant / Exposed. Seal / Monitor.


Additional Vent(s)
 ⠀⠀⠀⠀⠀⠀⠀⠀ Missing hood /Component(s). Install &/or Replace.

Exterior +
15
Focus Feature Page
These are photos related to the same component or system.


Balcony Access / Door(s)
‎Inspected for sealing, glazing, hardware, drainage, & signs of damage, air leakage, or intrusion.

Balcony Surface Material
‎Inspected to assess material condition, slope, surface wear & signs of damage,


Balcony Guards / Railing(s)
‎Inspected for attachments, height, stability, & signs of damage, movement, or deterioration.

The Balcony Baseline
Components are reviewed for presence, general condition, and visible signs of damage or deterioration where accessible. This includes the walking surface, guardrails, drainage, and visible structural connections. Accessible areas are checked for cracking, corrosion, rot, loose fasteners, and signs of water intrusion or improper slope. The review is limited to observable conditions without load testing, removing finishes, or evaluating concealed waterproofing or structural components.

Exterior +
16
Cladding / Material(s)
Inspected for cracks, gaps, clearance from grade, installation & surface deterioration. See also Insurance Section. Missing Bondo / Paint (minor). Seal & Repair .

Foundation / Structure
Inspected for flaking, cracking, displacement, moisture indicators & visible movement.

⚠️ SLOPE & Grade Management
Proper grading should slope away from the foundation, not remain flat or create negative slope that directs water toward the property. Watch for heaving, settling, and high or low spots that can trap moisture near walls. Ensure downspouts discharge well away from the structure and that gutters are level and draining correctly. Poor alignment or overflow can erode soil over time, increasing the risk of moisture intrusion and foundation movement.

Exterior +
17
⚠️ Exterior Observations
1. Missing parging on the foundation.
2. ​Paint touch-ups required on the garage side posts.
3. ​Bottom collars of the post starting to separate and split.
4. Missing cover plate for an intake vent on the balcony.
5. ​Exposed and unsealed nails visible on the Hardie Shingle/Plank siding in multiple locations.
6. Incomplete caulking and sealant application at the Hardie siding joints on the balcony and front entry.
7. ​Paint splatter and overspray present on the privacy wall surface.
8. ​Paint spotting and stains visible on the balcony threshold.
9. ​Excess silicone sealant bleeding out from the exterior penetration of the kitchen wall.
10. ​Paint transfer/splatter present on the metal flashing above the front entry door.
11. Concrete slurry splashed onto the Hardie siding near the front entry door.
12. ​Front entry downspout discharge has washed and displaced cedar mulch onto the front entry walkway.
13. ​Surface scuffs and blemishes observed on the front entry sliding Juliet door frame/glass.
14. Front door binding on latch side.
End Statement:
Routine maintenance and inspections are recommended, including cleaning gutters and reviewing roof materials from inside the attic. Seasonal or annual tune-ups are encouraged to replace damaged or aging segments.

Garage +
18
G BACK TO SUMMARY


Garage Overhead Door Motor(s)
Review focused on the support mount, basic operation, safety & visible indicators affecting function.


Garage Safety Track Sensor(s)
Observations included sensor presence, alignment, height & response during basic operational testing.

Garage Overhead Door(s)
Attention given to door panels, tracks, hardware, balance, & general operation. See also Insurance Section.

Garage +
19
⚠️ Garage General Notes
1. Missing mud and tape above the double door to the mechanical room.
2. ​Non-pressure-treated 2x4 being used to strap electrical conduit, which is also in contact with the garage slab floor.
3. ​Electrical conduit is not fully protected up to the panel.
4. ​Garage has not been swept and cleaned for the pre-possession walkthrough.
5. ​Holes in the drywall tape are visible in some areas of the garage.
6. Screws have not been fully taped in the garage.
7. ​Smoke seal is not continuous near the garage door backing.
8. ​Daylight is visible below the weather stripping of the garage door on the right-hand side.
9. ​Smoke seal is non-continuous by the man door leading into the home.
10. ​Concrete is splashed onto the man door threshold.
End Statement
Repairs, adjustments, cleaning, maintenance, and cosmetic improvements are recommended where required to improve appearance, functionality, and overall finish quality.

Attic
20
A BACK TO SUMMARY


The Hatch (Scuttle) Entry
Visually inspected for insulation & signs of damage, gaps, or air leakage at the opening.


Attic Hatch Weatherstrip

Sheathing / Roof Decking
Observations include material type, fastening pattern, visible sagging or deflection, moisture staining, delam & signs of past or active deterioration.

Insulation - Depth
Observations included insulation depth, vapour barrier presence, coverage consistency, & visible gaps. See also Insurance Section.

Interior
21
I BACK TO SUMMARY


Outlet(s)
Inspected for operation, secure mounting, polarity, grounding, cover condition & visible wiring concerns.


Interior Light(s)
Inspected for operation using normal switching procedures & visible deficiencies.

Interior Door(s)
Attention given to alignment, operation, hardware, hinges, latching, & indicators affecting use.


Door Hinge.

Interior Window(s)
Observations included glazing, operation, seals, & conditions affecting performance.


Window(s) & Operation
Review for opening, closing, latching, seals, weep holes & screens. See also Insurance Section.

Interior +
22
Heat Register(s)
For your records. Dirty / Consttuction Debris. Clean / Maintain.

Return Air Register(s)
For your records.

General Ceilings / Walls
Visually examined for common defects.

General Flooring
Visually examined for common defects.

Interior +
23
⚠️ Interior Observations
1 Missing doorstop at the front entry door.
2 Poor mitre joint noted to the right of the refrigerator on the second floor.
3 Minor construction dust, wood debris, and material remnants observed within select heat registers and cold air returns.
4 Minor dirt and debris accumulation noted within the Juliett patio door track.
5 Stairs leading to the third floor appear slightly angled to the right and may have experienced minor settlement. Condition was noticeable at the time of inspection.
6 Minor excess black caulking or sealant observed at the bottom of the stair assembly.
7 Minor cosmetic touch-ups are recommended at the stair nosing and adjacent left wall area.
8 Minor acoustic sealant residue was observed on select windows and would benefit from cleaning.
9 Missing lower doorstop at the upper front bedroom door.
10. Minor floor squeaks noted in upper floor hallway.
End Statement
Repairs, adjustments, cleaning, maintenance, and cosmetic improvements are recommended where required to improve appearance, functionality, and overall finish quality.

Interior +
24


Thermal Heat Supply

Thermal Ceiling(s)


Thermal Wall(s)

Thermal Window(s)


Thermal Door(s)

Hot Water Thermal


Thermal P-Trap(s)

Interior +
25
Main Panel


Breakers

Fixtures


Drains

The Thermal Baseline
Observervations of surface temperature variations that may indicate areas of heat loss, moisture intrusion, or abnormal electrical or mechanical conditions where accessible. The review is limited to visible thermal patterns on exposed surfaces and does not determine the exact cause of temperature differences. Findings are influenced by environmental conditions, building materials, and time of day. This review does not include destructive testing, internal wall inspections, or verification of concealed components, and is limited to observable conditions at the time of inspection.

Kitchen
26
K BACK TO SUMMARY


Kitchen Outlet(s)
‎Inspected for secure mounting, GFCI protection, polarity, grounding, cover condition & visible wiring concerns affecting safe use.


Microwave(s) ⠀

Refrigerator(s)
Inspected for operation, temperature control, door seal condition, water line connections, drainage, and general installation.


Dishwasher(s)
Inspected for operation, mounting, drainage & leakage indicators during short cycle.

Stovetop(s) / Cooktop(s)
Inspected for basic operation, burner function, surface condition & safety concerns.


Oven(s)
Inspected for operation, interior condition, door sealing & visible safety concerns.

Kitchen
27
Hood Fan(s) / OTR
Attention was given to general operation, connections, & ventilation path where visible. LOOSE FILTER

Kitchen Faucet(s), Sink(s) & Drain(s)
Reviewed, focused on operation, temperature, mounting, drainage, odors & leakage indicators.

Kitchen P-Trap(s)
Checked for drainage, trap configuration, connection security, leakage indicators & visible corrosion. Loose / Unsecure. Improve / Secure.

Kitchen +
28
Cabinetry & Drawer(s)
Noted. This has a core of hardwood or plywood with a layer of hardwood veneer applied to the top.

Backsplash & Countertop(s)
For your records.

General Ceilings / Walls
Visually examined for common defects.

General Flooring
Visually examined for common defects.

Kitchen +
29
⚠️ Kitchen Observations
1 Minor damage noted to the dishwasher gable panels on both sides.
2 Missing dishwasher cover plate.
3 Cabinetry is slightly out of level and would benefit from adjustment.
4 Minor evidence of past condensation observed at the kitchen window.
5 Minor construction-related scrapes noted to the window seal. Cosmetic repair or buffing may improve appearance.
6 Refrigerator is not level and should be adjusted.
7 Minor scratch noted to the granite countertop in front of the sink. Cosmetic repair or buffing may improve appearance.
8 Loose P-trap connection at the right sink drain knuckle. Tighten immediately to help prevent leakage.
End Statement
Repairs, adjustments, maintenance, and cosmetic improvements are recommended where required to improve appearance, support proper operation, and help prevent future deterioration.

Laundromat
30
L BACK TO SUMMARY


Water Supply & Hanmers
Reviewed, focused on plumbing connections, hoses, drains, seals & visible leakage.


Washer / Dryer NOT installed

240 V


Dryer Vent (Recessed)

Flooring


Outlet

Bathroom
31
B BACK TO SUMMARY


Bathroom Outlet(s)
Tested for anomalies.


Bathroom Extraction Fan(s)
Observations included basic operation & airflow response using simple draw testing. Not Working / No Function. Repair &/or Replace.

Overview Shower / Bathtub
Focused on fixtures, connections, operation, overflows & surrounds.


Plumbing Floor Drain(s)
Observations included drainage flow, blockage signs, backups, odors & leakage indicators.

Bathroom Water Faucet(s)
Operated to assess function, flow, mounting, sealing & signs of leakage, corrosion, or wear.


Bathroom Sink Drain(s)
‎ Slow Drain / Stopper Set Low. Repair &/or Replace.

Bathroom +
32
Bathroom P-Trap(s)
Checked for drainage, trap configuration, connection security, leakage indicators & visible corrosion.

Toilet(s)
Reviewed for stability, operation & visible leakage. X3 flush test per unit.

Bathroom +
33
General Ceilings / Walls
Visually examined for common defects.

General Flooring
Visually examined for common defects.

Bathtub & Surround(s)
Inspected for condition, secure installation, functional drainage, faucet operation, and visible signs of leaks, cracks, damage, or deteriorated sealant at accessible areas.

Mechanical
34
M BACK TO SUMMARY


Electrical Panel(s) ⠀
Assessing breakers, wires, bond, clearance, corrosion & damage.


The Main AMP
Generally, this will shut down everything! Designed to interrupt a large amperage load.

Hot Water Unit(s) ⠀
Attention was given to unit mounting, venting, safety components, temperature controls & visbile operation. Minor Rust @ Bottom. Clean / Repair / Maintain.


Hot Water Data
Unit detail(s). See also Insurance Section.

The Main Heating Unit(s)
Observations included mounts, venting, ducts, filters, clearances & visible performance.


Heating Unit Data Plate
Unit detail(s). See also Insurance Section.

Mechanical +
35
⚠️ Mechanical Observations
1 Missing foil tape at the humidifier duct connection.
2 HRV access panel improperly installed, preventing proper operation of the safety switch and potentially affecting unit functionality.
3 Mechanical room door spring-loaded hinges were not functioning as intended.
4 Excess low-voltage thermostat wiring was not neatly secured.
5 Main floor drain cover was missing.
6 Minor damage was observed to the hot water tank drain pan.
7 Minor rust staining was noted within the drain pan area.
End Statement
Repairs, modifications, maintenance, and general cleaning are recommended where required to improve safety, restore intended operation, and support long-term performance of the mechanical systems.

the

insurance

Overview Q&A
Site Limitations ⚠️ Visibility - Access - Height
Stairs & Handholds ◻️ Structure: Safe & Functioning as intended
Roof System
Roofing Surface ◻️ Material: Asphalt Cambridge - Age; Brand New
Exterior Overview
Cooling Type(s) ◻️ Not Present - Not Applicable (RI)
Envelope Cladding ◻️ Material: Fiber Smart Panel / Metal
Grade & Ground Cover ◻️ Terrain: Flat & Level - Vegitation
Attic System
Hatch & Insulation ◻️ Location: Prime Closet - Mat: Blown-In
Interior Overview
Walls & Ceilings ◻️ Material: Drywall / MDF
Flooring Surfaces ◻️ Material: LVP- Tile - Carpet
Kitchen & Bathroom
Safety - GFCI’s ◻️ Location: Kitchen: Present - Bath: Present
Laundry Specs ◻️ 220V - Vent: Metal - Water: Not Installed
Mechanical System
Heating Unit(s) ◻️ Type: HE Furnace / Forced Air - Age:2025
Water Heater Unit ◻️ Type: Electric Tank - Age:2025
Plumbing System ◻️ Public Water: PEX - City Sewer: ABS
Water Main Shutoff ◻️ Location: Mechanical Room / NO METER
Electrical System ◻️ Service: 200 AMP - Branch: Copper
Review Image

72 seconds

Positive reviews from awesome customers like you help others to feel confident about choosing our firm & our “to the point” reporting methodology.

We’d so appreciate if you could take 72 seconds to click on our logo below and share your happy experience.

Much Appreciated